BICSI Technician HW #2
The function of which type of cable is to provide interconnections between equipment rooms and
telecommunications rooms? - ✔✔Backbone cable
The main components of backbone cabling are cabling pa
...
BICSI Technician HW #2
The function of which type of cable is to provide interconnections between equipment rooms and
telecommunications rooms? - ✔✔Backbone cable
The main components of backbone cabling are cabling pathways, cables, miscellaneous support
facilities and which of the following? - ✔✔Connection hardware
What is the maximum length of a patch cord? - ✔✔16.4'
You are installing horizontal structured cabling in an open office environment with modular
furniture. You are using category 6A cabling. You have to terminate 22 cabling runs in each
modular furniture cluster of 11 units, and you are using MUTOAs. How many MUTOAs are
required for this application. - ✔✔1
How many transition points can you install in a horizontal cabling run? - ✔✔1
What color represents 1st level backbone cross-connect in a telecommunications room? -
✔✔White
What color represents the horizontal cabling cross-connect in a telecommunications room? -
✔✔Blue
Which class of administration of a SCS addresses infrastructure with multiple sight or campuses?
- ✔✔4
You are installing an outside plant cable into a building entrance. The customer is not concerned
about aesthetic appearance. They just want the cheapest and most easily maintained option. What
type of cable entrance would you use? - ✔✔Aerial
The main difference between an entrance facility and this room is that this room is generally
considered to be floor-serving as opposed to building serving facilities. - ✔✔TR
What is the space defined as a case or housing dedicated to the telecommunications function and
related support facilities. - ✔✔TE
What is the recommended minimum separation between telecommunications cable and electric
motors exceeding 5 kilovolt-amperes? - ✔✔48"
What type of telecommunications space generally houses equipment that serves and entire
building, campus, or customer? - ✔✔ER
What finished grade of plywood should be used in a telecommunications room? - ✔✔A/C
How far should toggle bolts be installed from the edge of a plywood backboard? - ✔✔2"
In a TR, on how many walls SHOULD cable tray be installed? - ✔✔All
Where should conduit ends be placed when a single piece of plywood is used as a backboard? -
✔✔On the left side
The size of one rack unit is - ✔✔1.75"
The maximum length of flexible conduit is - ✔✔20'
The largest hand bender is what size? - ✔✔1-1/4 trade size
It is suggested that open cable supports be used for no more than how many cables? - ✔✔50
What is the initial fill ratio factor of conduits when installing 2 cables? Assume straight runs with
now degrees of bend. - ✔✔31%
Open top cable supports should be installed to maintain a minimum of ________________inches
above ceiling tiles - ✔✔3
What is the point where the service provider network ends and the customer network begins? -
✔✔Demarcation Point
What is the maximum allowable horizontal cable length? - ✔✔295'
Which structured cabling topology places all network devices on one length of cable? - ✔✔Bus
What type of system is used to extend cellular coverage into a building to provide adequate
coverage throughout the inside of the building? - ✔✔DAS
Which cable provides an interconnections between Telecommunications spaces? - ✔✔Backbone
Cable
What is the maximum length of flexible conduit? - ✔✔20'
A cable that handles traffic between TRs in a single building is called - ✔✔Intrabuilding
backbone
How many levels of back cabling are there? - ✔✔2
Patch cords that are to be used as cross connects should be made of ___________ cable -
✔✔Stranded
How many outlets does BICSI recommend per work area - ✔✔2
The first cable to a work area should be at a minimum ____________ - ✔✔Cat5e
What is the color code for the Miscellaneous cross connect field? - ✔✔Yellow
Plywood SHOULD be installed on at LEAST _____________ walls in a TR - ✔✔2
Plywood should be painted with at least ___________ coat/s of fire retardant paint. - ✔✔2
If toggle bolts are used to hang plywood backboard, they should be spaced ________ apart. -
✔✔24"
What are the common depths of equipment racks? - ✔✔4" and 6"
What type of conduit should not be used inside commercial buildings? - ✔✔PVC